A camera that works on the bench but reboots at night, or a maglock that holds weakly at the far door, is very often a voltage drop problem. When I design ELV (extra-low voltage) systems, I check every DC run before choosing the cable. Here is the method I use.
The formula (DC, two-wire run)
Voltage drop (V) = 2 × L × I × ρ / A
- L = one-way cable length in metres (×2 because current goes out and comes back)
- I = load current in amps (use the device's maximum, e.g. with IR and heater on)
- ρ = resistivity of copper, about 0.0175 Ω·mm²/m at 20 °C
- A = conductor cross-section in mm²
Drop % = voltage drop / supply voltage × 100. A common design target for 12 V ELV loads is 10% or less, but the real limit is the minimum input voltage in the device datasheet.
Worked example 1: 12 V camera at 50 m
Camera: 12 V DC, 1.0 A max (IR + heater). Cable: 1.0 mm².
Drop = 2 × 50 × 1.0 × 0.0175 / 1.0 = 1.75 V = 14.6% → too much; the camera only sees about 10.25 V.
With 2.5 mm²: 2 × 50 × 1.0 × 0.0175 / 2.5 = 0.70 V = 5.8% → OK.
Minimum cable size for an allowed drop
Rearrange the formula: A = 2 × L × I × ρ / allowed drop (V)
For 10% of 12 V (1.2 V): A = 2 × 50 × 1.0 × 0.0175 / 1.2 = 1.46 mm². 1.5 mm² is right at the limit, so 2.5 mm² is the safer choice.
Worked example 2: 12 V maglock at 30 m
Maglock: 12 V DC, 0.5 A. Cable: 0.75 mm².
Drop = 2 × 30 × 0.5 × 0.0175 / 0.75 = 0.70 V = 5.8% → OK.
Practical tips from site work
- Use maximum current, not typical. IR LEDs and heaters can double a camera's draw at night, which is exactly when the reboots start.
- Several devices on one cable: add their currents for the shared section.
- Long runs: raise the supply voltage (24 V DC / 24 V AC devices), add a local power supply, or switch to PoE where possible. At 24 V, the same drop in volts is half the percentage.
- Real cable resistance is a little higher than the 20 °C value in hot ceilings and conduits, so keep some margin.