Sizing a UPS for a CCTV / Security Rack: Watts, VA, Battery Runtime and Heat
The five steps I use so the cameras keep recording when the power fails, with a worked 16-camera example

By Leo Anthony
2 min read
When the mains power fails, a security system has one job: keep recording. That depends on the UPS in the ELV rack, and UPS sizing goes wrong in three predictable ways: the load is guessed, the VA rating is read without the watt rating, and the battery runtime is taken from the nameplate Ah. Here is the method I use on every ELV (low-voltage) project, with a worked example for a 16-camera system.
Step 1: Add up the real load in watts
Example rack for a 16-camera system:
- NVR: 60 W
- 24-port PoE switch: 30 W own consumption + 16 cameras × 8 W = 158 W
- Core switch: 40 W
- Router / firewall: 20 W
Total = 278 W
Use the maximum PoE consumption of each camera (IR on, heater on), not the typical figure. The PoE cameras are powered through the switch, so they are part of the UPS load even though they sit outside the rack.
Step 2: Add a growth margin
Clients add cameras. Add 25% for future devices: 278 × 1.25 = 347.5 W, call it 348 W.
Step 3: Convert to VA and choose the UPS
VA = W ÷ power factor. With a power factor of 0.9: 348 ÷ 0.9 = 386 VA.
Don't run a UPS above about 80% of its rating: 386 ÷ 0.8 = 483 VA.
Now the trap: check both ratings on the datasheet. A "600 VA" unit is often only 360 W. 80% of 360 W is 288 W, which is below our 348 W, so it fails even though 600 VA looks bigger than 483 VA. In this example a 1000 VA / 900 W unit is the right choice.
Step 4: Battery energy for the required runtime
Battery Wh = Load W × runtime (h) ÷ inverter efficiency ÷ usable factor
For 30 minutes: 348 × 0.5 ÷ 0.9 ÷ 0.8 ≈ 242 Wh.
Second trap: lead-acid battery Ah ratings are usually given at the 20-hour rate. At a 30-minute discharge a lead-acid battery delivers much less, often around 55–60% of nameplate. So confirm with the manufacturer's runtime or constant-power table, or add an external battery pack. Never just multiply volts × Ah from the label.
Step 5: Heat load for the room
Heat (BTU/h) = W × 3.412
- Equipment: 348 × 3.412 ≈ 1,187 BTU/h
- UPS losses (about 10% of load, 35 W): 35 × 3.412 ≈ 119 BTU/h
- Total ≈ 1,306 BTU/h
In a small closed ELV room that needs ventilation or a small split unit. Heat is what kills UPS batteries: as a rule of thumb, every 8–10 °C above 25 °C roughly halves VRLA battery life.
Practical tips
- Put the NVR, the PoE switches and the core network on the UPS. Fire alarm and access control panels normally have their own standby batteries, sized to their own standards.
- Leave 20–30% free rack space (U) for growth and airflow.
- Re-run the numbers whenever cameras are added: the PoE switch load moves straight onto the UPS.
Do it in a spreadsheet
I keep rack U fill, UPS VA with power factor and growth, battery Wh for runtime and BTU/h heat in one workbook so the check is repeatable:
- ELV Rack, UPS & Heat Load Sizing Calculator (Excel): https://payhip.com/b/d8Gjp
- Free ELV Quick Calculator (CCTV storage, PoE budget, DC voltage drop): https://payhip.com/b/PUG1b
- All ELV workbooks in one download (CCTV, access control, fire alarm, PA, cabling BoQ, rack/UPS): https://payhip.com/b/R0uyW
Originally published on my ELV Design Notes blog: https://payhip.com/ChenYuELVTemplates/blog/elv-design-notes/ups-sizing-for-a-cctv-elv-rack-va-battery-runtime-and-heat-load-worked-example-excel-calculator
— Chen Yu, ELV / low-voltage systems design engineer